11/21/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1123-09637 (3609 S BELMAR AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Note and specify all piping materials (Black Iron, Gas line PEX, etc.), G2412.9.
2. Provide the length measured from the meter to the farthest attached appliance. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
3. Yellow tracer wire required for non-metallic pipe, G2415.17.3.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov