Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-1123-09525
Parcel: 12507589B

Address:
331 N OLSEN AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-1123-09525
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/28/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1123-09525 (331 N OLSEN AV TUCSON, AZ 85719)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Update the panel schedule with the correct wire size. The overcurrent protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper, Table E3702.14, Table E3705.5.3. All of your 20A and 30A breaker circuits have the incorrect wire size. Show a #6 awg wire size for circuits 22/24, 50A breaker, also include circuit description.
2. Show the feeder conductor from the meter to panel A sized according to E3705.1, Table E3705.1. The conductor type needs to be direct-burial rated, or wet location rated inside a conduit. E3406.5, E3803.
3. Protection of all interior 15A & 20A circuits serving outlet locations, per E3902.16. Update Arc-fault notes to include circuit numbers 10 and 23.
4. Combine all sheets into one construction document. Only provide the response letter as a separate file.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/28/2023 PDSD Application Completeness Express REVIEW COMPLETED