Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-1123-09508
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2023 | Site Engineering | NOT REQUIRED | |||
| 11/20/2023 | Site Zoning | NOT REQUIRED | |||
| 12/14/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/05/2023 | Residential Building | REQUIRES RESUBMIT | Clarify the electrical plan showing which outlets are existing. Otherwise, all are assumed as proposed for new installation. Include plan outlet numbering and a panel schedule if all outlets are proposed. 1. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2. 2. Show receptacle outlets at each kitchen counter space wider than 12” with no point along the wall line more than 24” from a receptacle outlet, E3901.4.1. Show receptacles within 2’ of counter edges or corners and no more than 4’ apart. 3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. 4. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6. 5. Hallways of 10’ or more in length require a receptacle, E3901.10. 6. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity. |
||
| 11/17/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |