Permit Number: TC-RES-1123-09508
Parcel: 125011450

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1123-09508
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2023 Site Engineering NOT REQUIRED
11/20/2023 Site Zoning NOT REQUIRED
12/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/05/2023 Residential Building REQUIRES RESUBMIT Clarify the electrical plan showing which outlets are existing. Otherwise, all are assumed as proposed for new installation. Include plan outlet numbering and a panel schedule if all outlets are proposed.

1. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
2. Show receptacle outlets at each kitchen counter space wider than 12” with no point along the wall line more than 24” from a receptacle outlet, E3901.4.1. Show receptacles within 2’ of counter edges or corners and no more than 4’ apart.
3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
4. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.
5. Hallways of 10’ or more in length require a receptacle, E3901.10.
6. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity.
11/17/2023 PDSD Application Completeness Express REVIEW COMPLETED