Permit Number: TC-RES-1123-09491
Parcel: 136350740

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.2

Permit Number - TC-RES-1123-09491
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/19/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1123-09491 (1520 S SLEEPY HOLLOW PL TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Residential systems with solar/ESS backfeed OCPD protection of 100A or greater, require a design and calculations provided by an Arizona registered Electrical Engineer, R106.1.
2. The #1/0 CU conductors are undersized for the given 200A fused OCPD. Provide conductor ampacity calculations. Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 240.21. The 200A fuses in the AC disconnect are less than the calculated ampacity of the #1/0 CU conductor of 154.7A.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov