Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-1123-09394
Parcel: 135110290

Address:
7501 E MARC PL

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-1123-09394
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/13/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1123-09394 (7501 E MARC PL TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. The total demand includes a furnace, but the furnace is not on the plans, please include the location of the furnace.
2. The 28-foot segment of 1-inch pipe is undersized for the demand supplied. Use 125’ in Table G2413.4(1) and supplied demand of 180 CF/h.
3. The ¾-inch segment supplying the stove and dryer is undersized for the given length and demand. Use 125’ in Table G2413.4(1) and supplied demand of 100 CF/h.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/13/2023 PDSD Application Completeness Express REVIEW COMPLETED