Permit Number: TC-RES-1123-09381
Parcel: 11820035B

Address:
1250 S 10TH AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1123-09381
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2023 Site Engineering NOT REQUIRED
12/04/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/20/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC).
No Wind Speed listed:
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability for 115 MPH, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems
2. Provide specific documentation for the micro inverters being used (ENPHASE IQ7PD-72-2-US) as the document provided is for the ENPHASE IQ7A-72-2-US.
Building_official@tucsonaz.gov
11/08/2023 PDSD Application Completeness REVIEW COMPLETED