Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1123-09233
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/03/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1123-09233 (1111 E LIMBERLOST DR Unit:UNIT 198 TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

No permit history could be found for the New HVAC unit. Provide permit documentation for the new HVAC unit or provide the information below.

Mechanical Plans:
1. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate the mechanical plans if system calculations will be provided by deferred submittal.

Electrical Plans:
2. Detail if this new HVAC requires a new electrical circuit or if it is installed in the same location of an old unit.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/02/2023 PDSD Application Completeness REVIEW COMPLETED