Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-1123-09222
Parcel: 12101614A

Address:
5930 E GRANT RD

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1123-09222
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/21/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT TC-RES-1123-09222 Resubmit comment

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Show compliance with interconnection requirements found in 705.12(B)(2)(1) or 705.12(B)(2)(2).
2. Provide the existing feeder size, 705.12(B)(2)(1)
3. Provide the length of the tap conductor, 240.21(B)

For any questions contact: building_official@tucsonaz.gov
01/22/2024 PDSD Application Completeness Express REVIEW COMPLETED