Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.2
Permit Number - TC-RES-1123-09222
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/06/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/06/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1123-09222 (5930 E GRANT RD TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. The tap at the Feeder is not compliant with NEC 705.12(B)(2)(1). Either the feeder needs to be upsized per 705.12(B)(2)(1)(a) or the 125A OCPD on the load side of the feeder needs to be downsized per 705.12(B)(2)(1)(b). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/04/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |