Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2023 Site Zoning APPROVED
11/20/2023 Site Engineering NOT REQUIRED
11/20/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/20/2023 Residential Building REQUIRES RESUBMIT TC-RES-1123-09220

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. All repairs shall be 2018 IRC compliant.

FLOOR PLANS:

1. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1.

STRUCTURAL PLANS:

1. Clarify if trusses, rafters, joist, or roof sheathing require repair, R106.1.

NOTES - DETAILS:

1. Clarify if appliances require replacement, R106.1.1.

ELECTRICAL PLANS:

1. Garage Receptacle Location: a 20 AMP receptacle outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services