Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1122-01116
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/30/2022 | Light Residential Building Review (OIP) | APPROVED | |||
| 12/06/2022 | Historic | NOT REQUIRED | Property is located within a National Register historic district and not within a locally listed Historic Preservation Zone/Historic Landmark. No Historic review is required. | ||
| 12/30/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/15/2022 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-RES-1122-01116 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: DENIED NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2. SPECIFY THE CODES AND LOADS USED IN THE DESIGN. NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM. BUILDING REVIEW COMMENTS: DENIED NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2. SPECIFY THE CODES AND LOADS USED IN THE DESIGN. NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM. VERIFY EQUIPMENT IS READILY ACCESSIBLE AS REQUIRED BY UTILITY COMPANY AND EMERGENCY PERSONNEL. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS9 DENIED NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2. SPECIFY THE CODES AND LOADS USED IN THE DESIGN. NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM. NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER. THE NEUTRAL AND GROUND ARE NOT SHOWN BONDED IN THE ELECTRICAL DIAGRAM OF THE MAIN DISCONNECT PANEL. NEUTRAL CONDUCTOR NOT SHOWN WITH FEEDERS TO SUBPANEL ON ACCESSORY DWELLING. SHOW GROUNDING ELECTRODE CONDUCTOR AND GROUNDING ELCTROCE DETAILS. SHOW THE COLD TEMPERATURE VOLTAGE CALCULATIONS. VERIFY EQUIPMENT IS READILY ACCESSIBLE AS REQUIRED BY UTILITY COMPANY AND EMERGENCY PERSONNEL. SPECIFY THE BACKFED BREAKERS ARE AT THE OPPOSITE ENDS OF THE BUSBARS FROM THE MAIN DISCONNECTS AND ADD THE REQUIRED LABEL REQUIRED BY SECTION 705.12(B)(2). SHOW EFFECTIVE LABEL AND DIRECTORY DESIGNS AND COLORS ON LIST OF LABELS SHEET. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
| 12/02/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |