Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1122-01111
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/30/2022 | Light Residential Building Review (OIP) | APPROVED | |||
| 12/30/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/15/2022 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-RES-1122-01111 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: DENIED NEED THE ENGINEERE'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2. NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM. THE SITE PLAN IS NOT DRAWN TO THE LISTED SCALE - THE N/S DIMENSIONS ARE AT A DIFFERENT SCALE THAN THE E/W DIMENSIONS. BUILDING REVIEW COMMENTS: DENIED NEED THE ENGINEERE'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2. NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM. NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER. THE SERVICE EQUIPMENT IS SHOWN BEING INSTALL OVER THE PROPERTY LINE - DETAIL HOW THE SAFE WORKSPACE AND LEGAL ACCESS OF THE EQUIPMENT BEING INSTALLED EXTENDING PAST THE PROPERTY LINE IS AND WILL BE MAINTAINED. SHOW THE VEHICLE IMPACT PROTECTION OF THE EQUIPMENT. THE SITE PLAN IS NOT DRAWN TO THE LISTED SCALE - THE N/S DIMENSIONS ARE AT A DIFFERENT SCALE THAN THE E/W DIMENSIONS. THE PANEL AREA APPEARS TO BE MORE THAN 33% AND REQUIRES A MINIMUM OF 3FT PATHWAY AT THE RIDGES PER SECTION R324.6.1 THE SITE PLAN DOES NOT SHOW A COMPLETE 3FT PATHWAY FROMTHE LOWEST ROOF EDGE TO THE RIDGE PER SECTION R324.6.2 - SHOW THE ROOF ACCESS POINTS MEETING THE REQIREMENTS OF SECTION R324.6 MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS9 DENIED NEED THE ENGINEERE'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING STRUCTURE. INCLUDE THE DEAD AND LIVE LOADS FOR PORTIONS OF THE ROOF COVERED BY PV PANELS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2. NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM. NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER. THE NEUTRAL AND GROUND ARE NOT SHOWN BONDED IN THE ELECTRICAL DIAGRAM OF THE MAIN DISCONNECT PANEL. THE SERVICE EQUIPMENT IS SHOWN BEING INSTALL OVER THE PROPERTY LINE - DETAIL HOW THE SAFE WORKSPACE AND LEGAL ACCESS OF THE EQUIPMENT BEING INSTALLED EXTENDING PAST THE PROPERTY LINE IS AND WILL BE MAINTAINED. SHOW THE VEHICLE IMPACT PROTECTION OF THE EQUIPMENT. THE SITE PLAN IS NOT DRAWN TO THE LISTED SCALE - THE N/S DIMENSIONS ARE AT A DIFFERENT SCALE THAN THE E/W DIMENSIONS. THE PANEL AREA APPEARS TO BE MORE THAN 33% AND REQUIRES A MINIMUM OF 3FT PATHWAY AT THE RIDGES PER SECTION R324.6.1 THE SITE PLAN DOES NOT SHOW A COMPLETE 3FT PATHWAY FROMTHE LOWEST ROOF EDGE TO THE RIDGE PER SECTION R324.6.2 - SHOW THE ROOF ACCESS POINTS MEETING THE REQIREMENTS OF SECTION R324.6 SHOW THE COLD TEMPERATURE VOLTAGE CALCULATIONS. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
| 12/02/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |