Permit Number: TC-RES-1122-01107
Parcel: 140383780

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1122-01107
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2022 Light Residential Building Review (OIP) APPROVED
12/30/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/15/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1122-01107

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
THE STRUCTURAL ANALYSIS CALCULATIONS ARE TO USE THE ROOF DEAD AND LIVE LOADS WHERE PANELS ARE LOCATED AS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2.
NEED THE RACKING INSTRUCTIONS SHOWING THE SPAN RATINGS OF THE SYSTEM BEING USED.


BUILDING REVIEW COMMENTS:
Denied
THE STRUCTURAL ANALYSIS CALCULATIONS ARE TO USE THE ROOF DEAD AND LIVE LOADS WHERE PANELS ARE LOCATED AS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2.
NEED THE RACKING INSTRUCTIONS SHOWING THE SPAN RATINGS OF THE SYSTEM BEING USED.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS9
Denied
THE STRUCTURAL ANALYSIS CALCULATIONS ARE TO USE THE ROOF DEAD AND LIVE LOADS WHERE PANELS ARE LOCATED AS DETAILED IN SECTION R324.4.1.1 CASES 1 AND 2.
NEED THE DERATION CALCULATIONS FOR THE CONDUCTORS.
NEED THE RACKING INSTRUCTIONS SHOWING THE SPAN RATINGS OF THE SYSTEM BEING USED

PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/01/2022 PDSD Application Completeness Express REVIEW COMPLETED