| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/01/2022 | PDSD Application Completeness Express | REQUIRES RESUBMIT | A 1" pipe size is undersixed for the total developed length and BTU. 1 1/4 at minimum would be required. Also note this would be the proper size to the first T branching to the appliances the appliances. |