Permit Number: TC-RES-1122-00858
Parcel: 13622073A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1122-00858
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2022 Light Residential Building Review (OIP) APPROVED
12/19/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/12/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1122-00858

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ROOF LOADING IS TO BE BASED ON THE DETAILS IN SECTION R324.4.1.1 FOR ROOF AREA COVERED BY PV PANELS.


BUILDING REVIEW COMMENTS:
Denied
THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ROOF LOADING IS TO BE BASED ON THE DETAILS IN SECTION R324.4.1.1 FOR ROOF AREA COVERED BY PV PANELS.
NEED THE RACKING INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM.
NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER.
DETAIL THE EXISTING AC UNIT REQUIRED WORKSPACE IS NOT OBSTRUCTED.
VERIFY EQUIPMENT IS READILY ACCESSIBLE AS REQUIRED BY UTILITY COMPANY AND EMERGENCY PERSONNEL.


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Denied
THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ROOF LOADING IS TO BE BASED ON THE DETAILS IN SECTION R324.4.1.1 FOR ROOF AREA COVERED BY PV PANELS.
NEED THE RACKING INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM.
NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER.
DETAIL THE EXISTING AC UNIT REQUIRED WORKSPACE IS NOT OBSTRUCTED.
VERIFY EQUIPMENT IS READILY ACCESSIBLE AS REQUIRED BY UTILITY COMPANY AND EMERGENCY PERSONNEL.
NEED THE COLD TEMPERATURE AND BIFACIAL CALCULATIONS MAXIMUM OUTPUT VOLTAGE FOR MAXIMUM MICROINVERTER INPUT.


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/23/2022 PDSD Application Completeness Express REVIEW COMPLETED