Permit Number: TC-RES-1122-00809
Parcel: 141367460

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1122-00809
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2022 Light Residential Building Review (OIP) APPROVED
01/04/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/04/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1122-00809

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING BUILDING.
NEED THE RACKING INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM.
NEED THE TILE HOOK INSTRUCTIONS AND INCLUDING SPANS AND BONDING REQUIREMENTS.


BUILDING REVIEW COMMENTS:
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING BUILDING.
NEED THE RACKING INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM.
NEED THE TILE HOOK INSTRUCTIONS AND INCLUDING SPANS AND BONDING REQUIREMENTS.
NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
DENIED
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING BUILDING.
NEED THE RACKING INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM.
NEED THE TILE HOOK INSTRUCTIONS AND INCLUDING SPANS AND BONDING REQUIREMENTS.
NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER.
SPECIFY THE BACKFED BREAKER IS AT THE OPPOSITE END OF THE BUSBAR FROM THE MAIN DISCONNECT AND ADD THE REQUIRED LABEL REQUIRED BY SECTION 705.12(B)(2).
THE NEUTRAL AND GROUND ARE NOT SHOWN BONDED IN THE ELECTRICAL DIAGRAM OF THE MAIN DISCONNECT PANEL.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/23/2022 PDSD Application Completeness REVIEW COMPLETED