Permit Number: TC-RES-1122-00794
Parcel: 10922006A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1122-00794
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2022 Light Residential Building Review (OIP) APPROVED
12/16/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/09/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1122-00794

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING BUILDING.


BUILDING REVIEW COMMENTS:
Denied
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING BUILDING.
NEED THE RACKING INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM.
DETAIL VEHICLE IMPACT PROTECTION AS NEEDED.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
NEED THE ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF THE EQUIPMENT AND THE EXISTING BUILDING.
NEED THE RACKING INSTRUCTIONS INCLUDING THE GROUNDING/BONDING DETAILS AND DIAGRAM.
NEED A DOCUMENT SHOWING THE MODULE COMPATIBILITY FROM THE RACKING MANUFACTURER.
NEED THE SPECIFIC DETAILS OF THE EMT BEING USED UNDERGROUND, RESISTANCE TO CORROSIONS, AND DEPTH.
NEED THE SPECS AND DETAILS OF THE COMBINER THAT IS NOTED TO BE A 125 A SUBPANEL WITH TWO 60AMP BREAKERS. THE CONDUCTORS AND FEEDER ARE NOT SIZED FOR THE OCPD IN THE FUSED DISCONNECT.
INCLUDE THE DERATING CALCULATIONS.
SHOW ALL REQUIRED LABELS INCLUDING RACEWAYS FOR DC CONDUCTORS PER SECTION 690.31(G)(3), DIRECTORIES, ETC
DETAIL VEHICLE IMPACT PROTECTION AS NEEDED.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/23/2022 PDSD Application Completeness Express REVIEW COMPLETED