Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1122-00697
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2022 | Light Residential Building Review (OIP) | APPROVED | |||
| 12/14/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/05/2022 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-RES-1122-00697 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied PENDING ELECTRICAL RESUBMITTAL APPROVAL BUILDING REVIEW COMMENTS: Denied PENDING ELECTRICAL RESUBMITTAL APPROVA MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied THE RT-MINI FOOT MOUNT IS NOT UL LISTED AND IS NOT INCLUDED IN THE IRONRIDGE LISTED RACKING SYSTEM SPEC SHEETS. NEED DETAILS OF PROPER BONDING/GROUNDING OF EACH MOUNTING FOOT SHOWN ON ENGINEERED PAGE OR EVIDENCE THAT THE FOOT IS INCLUDED IN THE UL LISTING AND APPROVED BY IRONRIDGE ALONG WITH INSTRUCTIONS FOR AN EFFECTIVE BONDING PATH. PAGE PV-04 NEEDS TO SHOW THE PROPER EFFECTIVE LABELING COLORS AND DESIGNS AS REQUIRED. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
| 11/21/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |