Permit Number: TC-RES-1122-00697
Parcel: 140181030

Address:
1226 E GARDEN LP

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1122-00697
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2022 Light Residential Building Review (OIP) APPROVED
12/14/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/05/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1122-00697

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
PENDING ELECTRICAL RESUBMITTAL APPROVAL


BUILDING REVIEW COMMENTS:
Denied
PENDING ELECTRICAL RESUBMITTAL APPROVA


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
THE RT-MINI FOOT MOUNT IS NOT UL LISTED AND IS NOT INCLUDED IN THE IRONRIDGE LISTED RACKING SYSTEM SPEC SHEETS. NEED DETAILS OF PROPER BONDING/GROUNDING OF EACH MOUNTING FOOT SHOWN ON ENGINEERED PAGE OR EVIDENCE THAT THE FOOT IS INCLUDED IN THE UL LISTING AND APPROVED BY IRONRIDGE ALONG WITH INSTRUCTIONS FOR AN EFFECTIVE BONDING PATH.
PAGE PV-04 NEEDS TO SHOW THE PROPER EFFECTIVE LABELING COLORS AND DESIGNS AS REQUIRED.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/21/2022 PDSD Application Completeness Express REVIEW COMPLETED