Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-1122-00695
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/29/2022 | Site Zoning | APPROVED | |||
12/01/2022 | Site Engineering | NOT REQUIRED | |||
12/04/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/29/2022 | Residential Building | REQUIRES RESUBMIT | 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. 2. Include all exterior fixtures on the property in the outdoor lighting calculations (OLC 3.1.2). The lumen limit applies to the entire property not each building. |
||
12/04/2022 | Fire New Construction | REVIEW COMPLETED | |||
11/29/2022 | PDSD Application Completeness | REVIEW COMPLETED |