Permit Number: TC-RES-1122-00695
Parcel: 125150600

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1122-00695
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2022 Site Zoning APPROVED
12/01/2022 Site Engineering NOT REQUIRED
12/04/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/29/2022 Residential Building REQUIRES RESUBMIT 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.
2. Include all exterior fixtures on the property in the outdoor lighting calculations (OLC 3.1.2). The lumen limit applies to the entire property not each building.
12/04/2022 Fire New Construction REVIEW COMPLETED
11/29/2022 PDSD Application Completeness REVIEW COMPLETED