Permit Number: TC-RES-1122-00693
Parcel: 133200680

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-1122-00693
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2023 Site Zoning APPROVED
01/17/2023 Site Engineering NOT REQUIRED
01/17/2023 Site Landscape NOT REQUIRED
02/09/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/09/2023 Fire New Construction REQUIRES RESUBMIT All buildings shall be within 400' of a hydrant unless SFR and owned not rented then shall be 600', IFC 507.5.1, new structure exceeds the 600' and therefore fire sprinklers shall be installed.

Questions:

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
01/17/2023 PDSD Application Completeness Express REVIEW COMPLETED
02/08/2023 Residential Building REVIEW COMPLETED