Permit Number: TC-RES-1122-00606
Parcel: 137118660

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1122-00606
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2022 Light Residential Building Review (OIP) APPROVED
12/12/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/06/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1122-00606

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
NEED AN ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF EQUIPMENT AND THE EXISTING BUILDING.


BUILDING REVIEW COMMENTS:
Denied
NEED AN ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF EQUIPMENT AND THE EXISTING BUILDING.
NEED THE RACKING INSTRUCTIONS INCLUDING THE GROUND/BONDING DETAILS AND DIAGRAM.
NEED A DOCUMENT SHOWING THE MODULE IS ALLOWED BY THE RACKING MANUFACTURER.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
NEED AN ENGINEER'S STRUCTURAL ANALYSIS REPORT FOR THE ADDITION OF EQUIPMENT AND THE EXISTING BUILDING.
NEED THE RACKING INSTRUCTIONS INCLUDING THE GROUND/BONDING DETAILS AND DIAGRAM.
NEED A DOCUMENT SHOWING THE MODULE IS ALLOWED BY THE RACKING MANUFACTURER.
DETAIL THAT THE BACKFED BREAKER IS LOCATED AT THE OPPOSITE END OF THE BUSBAR FROM THE MAIN DISCONNECT.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov