Permit Number: TC-RES-1122-00598
Parcel: 140441450

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1122-00598
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2022 Light Residential Building Review (OIP) APPROVED
12/12/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/06/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1122-00598

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
THE DRAWING PAGES DETAIL THAT 2"X2" TRUSSES WERE USED FOR THE ROOF FRAMING AND THE STRUCTURAL ANALYSIS DOES NOT DETAIL THE EXISTING FRAMING CONDITIONS


BUILDING REVIEW COMMENTS:
Denied
THE DRAWING PAGES DETAIL THAT 2"X2" TRUSSES WERE USED FOR THE ROOF FRAMING AND THE STRUCTURAL ANALYSIS DOES NOT DETAIL THE EXISTING FRAMING CONDITIONS.
NEED SCOPE OF WORK DETAILS OF HOW THE BRANCH CIRCUITS ARE BEING RELOCATED.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
NEED SCOPE OF WORK DETAILS OF HOW THE BRANCH CIRCUITS AND FEEDERS FOR THE BACKUP LOADS PANEL ARE BEING RELOCATED.
NEED THE STRING VOLTAGE OUTPUT AND COLD TEMPERATURE CALCULATIONS.
NEED DOCUMENTS SHOWING THE COMPATIBILITY OF THE LG CHEM BATTERY WITH THE SOLAR EDGE INVERTER.
THE ALTERED PANEL SCHEDULE SHOWN ON PAGE PV-6.1 DOES NOT SHOW THE REMOVAL OF THE CIRCUITS RELOCATED TO THE BACKUP PANEL.
THE FEEDERS FROM THE MAIN DISCONNECT TO THE HOUSE PANEL NEED TO INCLUDE AN EQUIPMENT GROUND, A GROUNDING ELECTRODE AT THE MAIN DISCONNECT, AND THE NEUTRALS AND GROUNDS IN THE HOUSE PANEL NEED TO BE SEPARATED. SHOW EXISTING FEEDER WIRE SIZES.
THE BREAKERS SHOWN IN THE ONE AND THREE-LINE DIAGRAMS FOR THE BACKUP PANEL DO NOT MATCH THE CIRCUITS BEING RELOCATED.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/17/2022 PDSD Application Completeness Express REVIEW COMPLETED