Permit Number: TC-RES-1122-00530
Parcel: 110110540

Address:
4741 E COPPER ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1122-00530
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2022 Site Engineering NOT REQUIRED
12/01/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/23/2022 Residential Building REQUIRES RESUBMIT TC-RES-1122-00530
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.
Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits
SITE PLAN:
1. Show the location of utility lines on the property, R106.1.1. Identify the utility lines requiring upgrade or replacement (i.e., Overhead Electrical Line).

FOUNDATION PLAN:
1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1. Show #4 rebar reinforcement with 3” clearance from earth, R403.1.3.5.3. Provide ½” anchor bolts with 7” embedment, R403.1.6. Provided 12” diameter footers are undersized.

FRAMING PLAN:
1. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity, R301.1. 2x12 rafters may not be used as a beam; consider a 4x12. 2x6 rafters may not span over 12’. Show 2x12 rafters @ 24”OC or 2x10 @ 16” OC.

SECTIONS - DETAILS:
1. Show the Post Section Detail with #4 rebar in the footing, R403.1.
2. Identify all fasteners for wind loading compliance. Show roof (uplift resistance) rafter fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.

ELECTRICAL PLANS:
1. Show the electrical service conductor on the site plan and if at the carport area show a overhead service conductor with an 8-foot clearance above the roof, E3604.2.1 or relocate the service panel from under the roof. The service line change or a new panel location must be coordinated with TEP for approval.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
520 837-4912
City of Tucson Residential Plan Review
11/28/2022 Site Zoning REQUIRES RESUBMIT ShapeShape

FROM: PDSD Zoning Review





PROJECT:



TC-RES-1122-00530

4741 E Copper St– R-1

Replace Carport (1st Review)





TRANSMITTAL: November 28, 2022

This site is located in the R-1 zone (UDC 4.9.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-3), subject to Use Specific Standards 4.9.7.B.5 - 9.



Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/23/2022 PDSD Application Completeness Express REVIEW COMPLETED