Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-1122-00519
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/23/2022 | Site Zoning | APPROVED | |||
| 12/01/2022 | Site Engineering | NOT REQUIRED | |||
| 12/01/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/23/2022 | Residential Building | REQUIRES RESUBMIT | 1. Notate if a gas reconnect is required with air pressure test. 2. Show receptacle outlets at each kitchen counter space wider than 12” with no point along the wall line more than 24” from a receptacle outlet, E3901.4.1. Show receptacles within 2’ of counter edges or corners and no more than 4’ apart. 3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. |
||
| 11/22/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |