Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-RES-1122-00479
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2023 | Site Zoning | NOT REQUIRED | |||
| 04/17/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/04/2023 | Residential Building | REQUIRES RESUBMIT | Show the location of the proposed service panel. TEP usually requires the shorted distance to the transformer. Show if the proposed service panel is a new single or dual meter base. Show any replaced feeder conductors to existing sub panels. All interior alterations require a floor plan for review. An interior subpanel requires a clear working space of 30” wide x 36” deep, E3405.2 and panelboards shall not be in clothes closets, in bathrooms, or over the steps of a stairway, E3405.5. |
||
| 03/17/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |