Permit Number: TC-RES-1122-00401
Parcel: 133502670

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1122-00401
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2022 Light Residential Building Review (OIP) APPROVED
12/09/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
12/09/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-1122-00401

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts
2. Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1 Show Calculations.


BUILDING REVIEW COMMENTS:
Approved
Installation of new PV system


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
Provide an electrical load calculation if reducing the main breaker rating.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov