Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.7
Permit Number - TC-RES-1122-00378
Review Name: RESIDENTIAL NEW DWELLING v.7
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/05/2024 | Site Zoning | APPROVED | |||
03/06/2024 | Zoning Modifications - DDO | APPROVED | |||
04/05/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
03/18/2024 | Residential Building | REQUIRES RESUBMIT | TC-RES-1122-00378 3rd PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. Structures built without a permit may require alteration for building code compliance. Provide a clear and concise construction plan set. Sample drawings are shown as an example: https://www.tucsonaz.gov/pdsd/residential-permits Provide a response letter indicating the plan set sheet number that provides a response to each comment. SITE PLAN: 1. Each structure attached to the dwelling should have an individual 3-foot clear space to the property line (including the roof projections) known as the fire separation distance for reducing fire spread to nearby buildings. Portions of buildings placed in a fire separation distance require one-hour fire-resistive construction in compliance with IBC Table 721.1(2). Provide a detail of the fire rated wall which is parallel to the side property line. FLOOR PLANS: 1. Identify the wall material between dwelling and proposed storage room for required fire spread separation (½” GWB equivalent), R302.6. STRUCTURAL PLANS: 1. Provide a Roof Framing Plan showing the location and size of all beams, headers, and rafters with appropriate spans for supporting live and dead structural loads, R804. SECTIONS - DETAILS: 1 Show a complete cross-section detail of the new exterior wall, R106.1.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5. 2 The framed wall may require a concrete stem for achieving the 6” clearance between framing and ground (R317.1 item 5). 3 Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended. If you have any questions, please contact: Ken Van Karsen (520) 791-5550 City of Tucson Residential Plan Review |
||
03/06/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |