Permit Number: TC-RES-1122-00378
Parcel: 133251390

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.5

Permit Number - TC-RES-1122-00378
Review Name: RESIDENTIAL NEW DWELLING v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/02/2024 Residential Building REQUIRES RESUBMIT Permit review TC-RES-1122-00378 (8437 E ROSEWOOD ST TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

Additional comments may be required when complete and updated building plans are submitted.

1. Only the site-plan file was uploaded. Please upload all the construction documents with the relevant fixes shown per our conversation with you, me, and Clayton.
2. Show complete fire-wall assembly with continuous foundation.
3. Show an extra support column under the main ridge beam,, with foundation, 10’ max span.
4. Make sure all the previous comments are addressed as well.

5. Contact Zoning for assistance with their specific comments as well.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/20/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-1122-00378
8437 E Rosewood St. - R-1
Attached Storage (4th Review)

TRANSMITTAL: December 20, 2023

Provide a detailed comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.
This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. This comment was not addressed. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. The following shall be provided on the plot plan.
a. This comment was not addressed correctly. No percentage of coverage was provided should be listed as 50%. Provide a lot coverage calculation on the plot plan. This calculation shall meet the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements.
Once the required plot plan is provided additional comments may be forth coming.

2. This comment was not addressed. No building elevations have been provided. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Provide fully dimensioned building elevations so that perimeter yard setback requirements can be verified.

3. This comment was not addressed. There is no neighbors setback waiver provided for the owners to the east. Since you have called the structure located along the east property line as what appears to be “DETACHED” a neighbors setback waive will be required to reduce the perimeter yard setback. To secure this neighbor setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s):
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________
The setback waive is required to be placed on the plot plan.

4. This comment was not addressed. There is some type of structure attached to the east side of the existing dwelling. Zoning was not able to fine approve permit documents for this structure. Either provide copies of approved permit documents with the next submittal or include this structure with this permit.

As it appears that the attached structures are not meeting perimeter yard setbacks. Minimum setbacks for this site to the north, east and west property lines is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). At a minimum a Design Development Option (DDO) will be required. If any of the setbacks are less than 1’-0” the DDO will not work to reduce the required setback and a Board of Adjustment for Variance maybe required.

DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/22/2024 Zoning Modifications - DDO REQUIRES RESUBMIT The submitted DDO application has been deemed complete by staff. If the DDO is approved, provide a copy of your DDO decision letter in addition to a revised plan set and a comment response letter.

If you have questions about this transmittal, please email me at georgia.pennington@tucsonaz.gov.
12/14/2023 PDSD Application Completeness Express REVIEW COMPLETED