Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1026-05875
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/23/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/23/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Clarify scope of work, this states a service entrance upgrade. What are the individual components being replaced. A service panel upgrade must provide the Surge Protector Device, if applicable. Please provide the model # of the SPD to be install, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67 |
||
| 10/22/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |