Permit Number: TC-RES-1026-05866
Parcel: 140440280

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1026-05866
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/23/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov

Please resubmit addressing the following comments:
1) Please provide the model # of the Surge Protection Device (SPD) to be installed, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67
10/22/2026 PDSD Application Completeness Express REVIEW COMPLETED