Permit Number: TC-RES-1026-05832
Parcel: 123171660

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-1026-05832
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2026 Residential Engineering NOT REQUIRED
10/27/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/26/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-1026-05832
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review includes architectural, plumbing, mechanical, energy conservation and electrical compliance with the 2024 International Residential Code and 2024 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 code compliance.

Place the current 2024 IRC reference code on the Site Plan and number each sheet of the plan set.

Submit a separate permit application for the site wall and gates.

Provide a separate response letter addressing each comment with location of change on the plans.

Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Show the location of the electrical service panel, R106.1.1.

MECHANICAL PLANS:

1. Show any HVAC system changes, R325.8, M1401.3, M1601.1.

PLUMBING PLANS:

1. Show any plumbing system changes including the water heater, R106.1.1.

ELECTRICAL PLANS:

1. Show any electrical changes, R106.1.1.
2. Clarify if the light fixtures at new or existing, E3903.3. Show the location of each new fixture on the floor plan.
3. Smoke alarms are required within and outside of each sleeping room, R310.2.2 & R310.3.2.
4. New and extended 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
10/26/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Roxanne Johnston, Planner

PROJECT: TC-RES-1026-05832
1416 E Drachman St., Tucson, AZ 85719
SFR Renovations (1st Review)
Ref: CE-VIO1026-04290

TRANSMITTAL DATE: 10/27/2026

This site is located within the R-2 Zone (UDC 4.7.9). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.

1. Please provide a “Full” site plan as the renovations were related to code violation CE-VIO1026-04290: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Site-Plan-Examples

2. Please apply for a separate fence/wall permit as it is unable to be combined with the renovation permit. When applying for the wall permit, please note that residential zoning requires a ‘Basic’ site plan for the wall permit application, found here: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Site-Plan-Examples

3. With next submittal, please include the following:

a. “Full” site plan as the renovations were related to code violation CE-VIO1026-04290: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Site-Plan-Examples

b. A note on the full site plan stating the wall(s) will be permitted separately, e.g. ‘by separate permit.’ with an arrow pointing to the fence/walls.

c. Response letter explaining how all staff comments have been addressed.

4. Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted for the next review.

If you have any questions about this transmittal, please contact Roxanne Johnston at roxanne.johnston@tucsonaz.gov .
10/23/2026 PDSD Application Completeness Express REVIEW COMPLETED