Permit Number: TC-RES-1026-05788
Parcel: 140324800

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1026-05788
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2026 Residential Zoning APPROVED
10/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/16/2026 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
1) Please show adherence to R330.8 Protection from Impact. ESS is placed within a drivable portion of the driveway, verify the height/location of ESS if relocated. If the ESS remains in the driveway, please use of the methods depicted in R330.8.3 or show return wall exceeds depth of ESS equipment.
2) The sum of supply sources (90A) exceeds the maximum allowable capacity (65A) for this 200A busbar. The main breaker rating plus all back fed breakers must not exceed 120% of the busbar rating per NEC 705.12(B)(1)
10/16/2026 PDSD Application Completeness Express REVIEW COMPLETED