Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1026-05788
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2026 | Residential Zoning | APPROVED | |||
| 10/19/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/16/2026 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Please show adherence to R330.8 Protection from Impact. ESS is placed within a drivable portion of the driveway, verify the height/location of ESS if relocated. If the ESS remains in the driveway, please use of the methods depicted in R330.8.3 or show return wall exceeds depth of ESS equipment. 2) The sum of supply sources (90A) exceeds the maximum allowable capacity (65A) for this 200A busbar. The main breaker rating plus all back fed breakers must not exceed 120% of the busbar rating per NEC 705.12(B)(1) |
||
| 10/16/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |