Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1026-05771
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/16/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Provide a comment response letter and address the following comments: 1) The load calculation lists the EVSE is rated at 11,500 VA. Due to nature for a continuous load like an EV charger, the circuit must be rated at 125% per-625.41. The minimum size for this continuous load is 60A, the breaker, conductors, and outlet must be rated for 60A. |
||
| 10/16/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |