Permit Number: TC-RES-1026-05741
Parcel: 117084290

Address:
424 W 19TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-1026-05741
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2026 Residential Engineering NOT REQUIRED
10/20/2026 Residential Zoning NOT REQUIRED
10/22/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/22/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-1026-05741
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review includes architectural, plumbing, mechanical, energy conservation and electrical compliance with the 2024 International Residential Code and 2024 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 code compliance.

Provide a separate response letter addressing each comment with location of change on the plans.

ELECTRICAL PLANS:

1. Show a wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3.
2. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
3. Provide GFCI protection for appliance receptacle outlets, E3902.12 & 14. Include the dishwasher, electric range and microwave oven.
4. Show a wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
10/16/2026 PDSD Application Completeness Express REVIEW COMPLETED