Permit Number: TC-RES-1026-05718
Parcel: 141202280

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-1026-05718
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/16/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Provide a comment response letter and address the following comments:
1) Redline comment indicates "Similar, not exact". Provide the exact outlet to determine Amperage will be 40A or 50A.
2) Breaker must be rated at 50A as the EV Charger is rated at 9600VA. Overcurrent protection for feeders and branch circuits supplying EVSE and WPTE, shall be sized for continuous duty and shall have a current rating of not less than 125 percent of the maximum load of the equipment 625.41
10/16/2026 PDSD Application Completeness Express REVIEW COMPLETED