| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/16/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Provide a comment response letter and address the following comments: 1) Redline comment indicates "Similar, not exact". Provide the exact outlet to determine Amperage will be 40A or 50A. 2) Breaker must be rated at 50A as the EV Charger is rated at 9600VA. Overcurrent protection for feeders and branch circuits supplying EVSE and WPTE, shall be sized for continuous duty and shall have a current rating of not less than 125 percent of the maximum load of the equipment 625.41 |
||