Permit Number: TC-RES-1026-05718
Parcel: 141202280

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1026-05718
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/15/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Provide a comment response letter and address the following comments:
1) OCPD must be sized to meet the rating of the outlet. Therefore, the size of the breaker is undersized (50A breaker)
2) The load calculation lists the EVSE is rated at 11,500 VA. Due to nature for a continuous load like an EV charger, the circuit must be rated at 125% per 625.41. The minimum size for this continuous load is 60A, the breaker, conductors, and outlet must be rated for 60A.
10/14/2026 PDSD Application Completeness Express REVIEW COMPLETED