| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/15/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/15/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Provide a comment response letter and address the following comments: 1) OCPD must be sized to meet the rating of the outlet. Therefore, the size of the breaker is undersized (50A breaker) 2) The load calculation lists the EVSE is rated at 11,500 VA. Due to nature for a continuous load like an EV charger, the circuit must be rated at 125% per 625.41. The minimum size for this continuous load is 60A, the breaker, conductors, and outlet must be rated for 60A. |
||
| 10/14/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |