Permit Number: TC-RES-1026-05703
Parcel: 133571630

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-1026-05703
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/22/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
The following comments were not addressed. Please carefully read, provide a comment response letter acknowledging comments, and demonstrate how the comments were corrected on the plan set.
General:
1) A permit has not been submitted for a spa, please verify if the spa will be installed on a separate permit or provide the permit number for the spa permit.
Electrical:
1) Provide load calculations for the new load (Standard or Optional is accepted). As of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code
2) Outdoor receptacle 50A or less must be GFCI protected. 210.8(F)
10/21/2026 PDSD Application Completeness Express REVIEW COMPLETED