Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-1026-05703
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/22/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: The following comments were not addressed. Please carefully read, provide a comment response letter acknowledging comments, and demonstrate how the comments were corrected on the plan set. General: 1) A permit has not been submitted for a spa, please verify if the spa will be installed on a separate permit or provide the permit number for the spa permit. Electrical: 1) Provide load calculations for the new load (Standard or Optional is accepted). As of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code 2) Outdoor receptacle 50A or less must be GFCI protected. 210.8(F) |
||
| 10/21/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |