Permit Number: TC-RES-1026-05703
Parcel: 133571630

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1026-05703
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/13/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
General:
1) A permit has not been submitted for a spa, please verify if the spa will be installed on a separate permit or provide the permit number for the spa permit.
Electrical:
1) Provide load calculations for the new load (Standard or Optional is accepted). As of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code.
2) Identify conductors including current-carrying conductors, grounded conductors, and EGCs
3) Show if conductors will be above or below ground. Include depth and attachment details in accordance with E3801
4) Show distance of receptable from inside wall of spa, receptacle must be GFCI E4203.1.4 E3902.3
5) All equipment must be listed for wet locations E3905.11
10/13/2026 PDSD Application Completeness Express REVIEW COMPLETED For questions: PDSD-Permits@tucsonaz.gov.

A separate permit is required for the spa under a Residential Pool/Spa Permit.