Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1026-05481
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/01/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Provide a comment response letter and address the following comments: 1) Provide load calculations including the EV charger (Standard or Optional are accepted). As of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code. EVSE to be calculated at a minimum of 7.2 kW or nameplate rating, whichever is greater. Conductors and OCPDs are to be sized as continuous loads (80% rule) 220.10 2) Provide Manufacturer Specifications of the EV charger to be used. Include any certifications to ensure that the EVSE is UL listed E3403.3 3) EV charger must be GFCI-capable, alternatively provide a means of GFCI protection (including GFCI Overcurrent Protection Devices (OCPD)) 625.54 |
||