10/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/01/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Provide a comment response letter and address the following comments:

1) Provide load calculations including the EV charger (Standard or Optional are accepted). As of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code. EVSE to be calculated at a minimum of 7.2 kW or nameplate rating, whichever is greater. Conductors and OCPDs are to be sized as continuous loads (80% rule) 220.10
2) Provide Manufacturer Specifications of the EV charger to be used. Include any certifications to ensure that the EVSE is UL listed E3403.3
3) EV charger must be GFCI-capable, alternatively provide a means of GFCI protection (including GFCI Overcurrent Protection Devices (OCPD)) 625.54
10/01/2026 PDSD Application Completeness Express REVIEW COMPLETED