Permit Number: TC-RES-1025-05319
Parcel: 113095460

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-1025-05319
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2026 Residential Engineering APPROVED
03/11/2026 Residential Zoning APPROVED
03/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/26/2026 Residential Building REQUIRES RESUBMIT TC-RES-1025-05319 2nd
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance.

Provide a separate response letter addressing each comment with location of change on the plans.

PLANS:

1. Notate a cool (white) roof finish (greater than 60 SRI) as required by the ADU provisions.
2. Provide a Roof Framing Plan showing the rafters sized for supporting live and dead structural loads (Table R802.4.1(1)). Sheet 4 shows 2 x 12 joists spanning the 30’ wide building. Change the joist type or add a load bearing wall between the dwelling and storage room with a foundation.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm outside the bedroom doorway.
2. The dishwasher with GFCI readily accessible protection typically from an upstream device, E3902.9 & 10.

OUTDOOR LIGHTING CODE

1. Update the Outdoor Lighting Calculation with an approved property area entry, OLC 401.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
02/24/2026 PDSD Application Completeness Express REVIEW COMPLETED