Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADD/ALT v.6
Permit Number - TC-RES-1025-05099
Review Name: RESIDENTIAL ADD/ALT v.6
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/31/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/31/2026 | Residential Building - Standard | REQUIRES RESUBMIT | TC-RES-1025-05099 5th PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections. Note the 2018 IRC reference on the plans. Provide a response letter addressing each comment with location of change on the plans (sheet number). Provide a complete construction plan set with a sheet number on each page. Remove the comment response notes from the construction plans. Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits SECTIONS - DETAILS: 1. Provide a proposed wall section detail for the proposed exterior framed (insulated) wall enclosing the vehicle door opening, R403.1.6. Show the concrete stem with the wall sheathing at 6” clearance above the ground or 2” above a paved area, R703.7.2.1. 2. Clarify the placement of ceiling/roof insulation with either a ventilated attic or sealed rafter cavity, R806. Remove the bird boards if there is not a vented attic between roof sheathing and insulation. Show a layer of rigid foam board between the roof sheathing and batt insulation for an unvented roof assembly. PLUMBING PLANS: 1. Provide a plumbing plan showing water supply, drain, and vent pipe locations and sizes R106.1.1. MECHANICAL PLANS: 1. Show the location of the mini-split system on the plans, M1401.3, M1601.1. ELECTRICAL PLANS: 1. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2. 2. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6. 3. Note the requirement for arc-fault interrupter circuit, E3902.16. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Show compliance with the energy code requirements for placement of wall insulation (R-13 in 2x4 framing or R-19 in 2x6 framing) at all exterior walls, N1102.1. If you have any questions, please contact: Kenneth.VanKarsen@tucsonaz.gov City of Tucson Residential Plan Review ---------------------- |
||
| 03/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |