10/21/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Please resubmit addressing the following comments:
1) Clarify if this will be a new system or modifying the existing system
2) Provide HVAC demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D.
3) If applicable, please provide electrical load calculations for determining the service panel can support the additional electrical load, E3602.2. please include OCPD and conductor for the electrical.
4) Provide location of condensate drain line and disposal from HVAC unit, M1411.3