Permit Number: TC-RES-1025-05050
Parcel: 132111580

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1025-05050
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/16/2025 Addressing Validation REQUIRES RESUBMIT It appears that 2 panels are being replaced. Each panel replacement requires a separate permit. Please proceed with this permit for 2742 S FORGEUS AV and apply for a second trade permit for the panel replacement for 2744 S FORGEUS AV. Also the site plan must include the full project address. Please resubmit the site plan once the review is done and include the full project address on it.
Step-by-step instructions on how to upload the site plan to this permit:
https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
For questions: PDSD-Residential@tucsonaz.gov
10/16/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Please resubmit addressing the following comments,
1) Please include an aerial site plan including the proposed location of the Main service panel. Include the address
2) TEP requires 2' minimum rigid conduit risers, please refer to the 2025 ESRB for TEP guidelines for clearances and installation requirements
3) Demonstrate compliance with NEC 230.2 (Number of Services). A second metered electrical service is not applicable under the current permit. Please apply for a second Residential Trade permit for the other address
For any questions, please email me: juan.quintana@tucsonaz.gov
10/16/2025 PDSD Application Completeness Express REVIEW COMPLETED