Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-1025-04901
Parcel: 130080830

Address:
3723 E GARDEN ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.3

Permit Number - TC-RES-1025-04901
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/24/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Please resubmit addressing the following comments:
1) The X" pipe is undersized for the given length and appliance demand. Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) (Polyethylene Plastic Pipe), or Manufacturer’s sizing requirements.
If you have any questions, please email: juan.quintana@tucsonaz.gov
10/24/2025 PDSD Application Completeness Express REVIEW COMPLETED