Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1024-06100
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/21/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1024-06100 (4481 E LA JOLLA CI TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide an updated Plan and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received. For questions: Building_Official@tucsonaz.gov 1. Pipe size 3/4'' from gas meter rise to the farthest attached appliance is undersized must be a minimum of 1'' per Table G2413.4(1). - See drawing for markups. 4. Missing pipe size from segment to the furnace and must be a minimum on 3/4'' per Table G2413.4(1). - See drawing for markups. |
||
| 10/21/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |