10/21/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1024-06100 (4481 E LA JOLLA CI TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide an updated Plan and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received. For questions: Building_Official@tucsonaz.gov

1. Pipe size 3/4'' from gas meter rise to the farthest attached appliance is undersized must be a minimum of 1'' per Table G2413.4(1). - See drawing for markups.

4. Missing pipe size from segment to the furnace and must be a minimum on 3/4'' per Table G2413.4(1). - See drawing for markups.