Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1024-06027
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/21/2024 | Site Engineering | NOT REQUIRED | |||
10/24/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/24/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1024-06027 (7558 S CIRCULO RIO BLANCO TUCSON, AZ 85756) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Conductors in Raceway# 2-4 are undersized. OCPD(Breaker) for copper conductor may not exceed 30A for #10 AWG conductors as required by IRC E3705.5.3, NEC 240.4(D)(small conductors), For larger than #10AWG, see NEC Table 310.15(B)(16) Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
10/16/2024 | PDSD Application Completeness | REVIEW COMPLETED |