Permit Number: TC-RES-1024-06027
Parcel: 141366470

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1024-06027
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2024 Site Engineering NOT REQUIRED
10/24/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/24/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1024-06027 (7558 S CIRCULO RIO BLANCO TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Conductors in Raceway# 2-4 are undersized. OCPD(Breaker) for copper conductor may not exceed 30A for #10 AWG conductors as required by IRC E3705.5.3, NEC 240.4(D)(small conductors), For larger than #10AWG, see NEC Table 310.15(B)(16)