Permit Number: TC-RES-1024-05930
Parcel: 12007268B

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1024-05930
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2024 Site Engineering NOT REQUIRED
10/14/2024 Site Landscape NOT REQUIRED
11/14/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/24/2024 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-1024-05930 (137 W DISTRICT ST TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).


General:
1. Update the site plan to show the storage shed as existing, not new.
2. Show the measurement from the property line to the new bedroom wall.

Framing Review:
1. Provide complete roof and floor framing plans. Show size, spacing and span of all framing members, trusses, joists, rafters, beams, glue-lams, lintels, headers, ledgers and blocking, R301.1.
2. Provide a complete roof framing plan with beams and rafters sized with appropriate prescriptive load carrying capacity, R301.1 or provide an engineer’s sealed plan set for performance compliance consideration, R301.1.3.
3. Provide the location of existing load bearing walls or roof supporting structures for verifying new beam and rafter sizes, R301.1.
4. Bedrooms require compliant egress to the exterior. Include dimensions and show all doors and windows in the construction area, R310.
5. Show compliance with R310 providing egress from bedrooms with minimum net clear opening area of 5.7 SQ FT (5 SQ FT 1st floor). Also, show the minimum net clear opening dimension of 24” height and 20” width, and maximum sill height of 44”.

Electrical Review:
6. Show the location of each outlet on the Electrical Plan, E3404.12.
7. Show a receptacle outlet within 3’ of each lavatory basin in each bathroom, E3901.6. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.
8. Protect extended branch circuits with combination type arc-fault circuit interrupters, or an AFCI type receptacle at the first outlet on the branch circuit, E3902.17.
9. Update the last Electrical Note to reference the correct judication and code year, City of Tucson and 2018 IRC. Arc-Fault protection shall comply with E3902.16 and E3902.17
10. Show locations of each smoke alarm, R314. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity.

Detail and Energy Review:
11. Provide an attic space ventilation calculation and specify size and location of all vents needed to comply with R806.2 if using a vented attic design. Or show an unvented roof assembly.
12. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance and may be a single layer of air-impermeable insulation or layered with batt insulation for achieving the total required roof R-value (R-30 for addition <20%).
13. Tucson is in climate zone 2B. Show compliance with the simplified prescribed energy values for glazing is U=0.40 with a solar heat gain coefficient SHGC minimum value of 0.25, N1102.1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/05/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Ramiro Olivarez
Planner, Zoning Review Section

PROJECT: TC-RES-1024-05930
137 W DISTRICT ST TUCSON, AZ 85714 – R-2 Zoning
Bedrooms and Bathroom Extension (1st Review)
TRANSMITTAL DATE: 11/05/2024

General Comments

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

The site plan should be designed to include the information as noted on the sample plot plan. See the link below for the information that is required on the plot plan. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements.pdf.

Zoning Review Comments

1. Comment: Update the project description from “storage shed” to “Bedrooms and Bathroom Extension”.
2. Comment: Recalculate and update the Lot Coverage Calculations to include the new project extension.
3. Comment: Update the site plan to show the storage shed as existing, not new.
4. Comment: Remove all the previous City stamp approvals from the plans.
5. Comment: Draw, label, and dimension the setback from the west property line to the proposed addition.
6. Comment: Provide an elevation sheet with a drawn, labeled, and dimensioned height of the wall. The wall height is measured from design grade (the ground) to the top of the wall. This is to ensure the project meets setback compliance.
7. Comment: It appears sometime after 2021 the Rear porch has had alteration work done without permits. No permit history for this alteration can be found on Property Research Online (https://pro.tucsonaz.gov/address_search/137/W/DISTRICT/ST). This porch alteration will need to be permitted. Zoning will not be able to approve the bedroom extension without the approval of the porch alteration. The porch alteration with its construction plans may be included as a part of this permit application.
8. Comment: Additional comments may be forthcoming on the next review based on the proposed use for the addition and applicable use specific standards.

If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov
10/14/2024 PDSD Application Completeness Express REVIEW COMPLETED