Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1024-05925
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/14/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/14/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1024-05925 (1432 E MOSSMAN RD Unit:UNIT 26 TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide an updated Plan and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received. 1. Clarify the scope of work being performed, R106.1. Highlight the portions of the line being new or replaced. 2. Pipe size from meter to the farthest attached appliance is undersized must be a minimum of 1'' per Table G2413.4(1). 3. Pipe size dropping down to range is also undersized must be a minimum of 1'' per Table G2413.4(1). 4. Missing pipe size from segment to the furnace and must be a minimum on 3/4'' per Table G2413.4(1). - Please see attachment for markups. |
||
10/14/2024 | PDSD Application Completeness | REVIEW COMPLETED |