Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2024 Residential Building APPROVED
11/06/2024 Site Engineering NOT REQUIRED
11/06/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/30/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Ramiro Olivarez
Planner, Zoning Review Section

PROJECT: TC-RES-1024-05828
6829 E NELSON DR TUCSON, AZ 85730 – R-1 Zoning
Attached Rear Home Porch (1st Review)

TRANSMITTAL DATE: 10/30/2024

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9

General Comment: Please resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.

General Comment: The site plan should be designed to include the information as noted on the sample plot plan. See the link below for the information that is required on the plot plan. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements.pdf.


1. Comment: Label on the site plan the zone (R-1) and all the adjacent property zones. Or show a zoning detail of this properties zone and all adjacent property zones. (As noted on the sample plot plan above)
2. Comment: Draw, label, and dimension the setbacks to the proposed porch from all property lines. Remove the front yard 6-foot setback line as that is not the minimum front perimeter yard setback. (As noted on the sample plot plan above)
3. Comment: Lot Coverage shall include the total lot coverage calculations. Per UDC article 6.4.3, lot coverage shall need to include the area of a lot covered by buildings, storage areas, including dimensioned vehicular use areas. Do not include the porch square footage in the total lot coverage calculations. (Porches open on at least one side are not included in the calculation) (As noted on the sample plot plan above)

3A: There appears to be a tall structure at the entryway of the home. Provide the height of this structure to ensure compliance with maximum height.

4. Comment: Ensure the scale measurement is accurate. Using the 1:1 scale (as indicated on the plans) measurements do not appear accurate.
5. Comment: On the elevation sheet show the dimensioned height of the proposal from design grade (the ground) to the top of the beam. To ensure setbacks are met.
6. Comment: Clarify is the proposed demo to be the rear home porch addition (unpermitted and appears sometime between 2010 to 2012) found in recent aerial views.
7. Comment: Additional comments may be forthcoming on the next review based on the proposed use for the addition and applicable use specific standards.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Provide updated site & elevation plan in the next submittal.

If you have any questions about this transmittal, please contact Ramiro Olivarez Ramiro.Olivarez@tucsonaz.gov