Permit Number: TC-RES-1024-05785
Parcel: 12910126A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1024-05785
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/07/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Modifications to the gas line may require that the existing system be enlarged to meet the total demand based on the new length and load, or a new dedicated line is required for the additional attached loads, G2412.3, G2412.4.
Provide manufacturer’s spec sheet demonstrating Appliance fuel input or use prescriptive number in gas piping template, R106.1.1. https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/gas_piping_template.pdf
Provide a complete gas piping template showing the connection and length from the meter to all attached appliances, G2401.1, R301.1: Include pipe size, type (Black Iron, Poly) and length. Provide appliance demands, G2413.4.1.
Provide total demand from all appliances, G2413.2.
Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
The ¾” pipe to the tankless water heater and Range is undersized for the given length and appliance demands. Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) (Polyethylene Plastic Pipe), or Manufacturer’s sizing requirements. Resubmit gas piping template with all the proper information filled out.

https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/gas_piping_template.pdf

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf if you have any further questions or concerns you can reach me at building_official@tucsonaz.gov.
10/07/2024 PDSD Application Completeness Express REVIEW COMPLETED